Assembly of a CPU 41x–H
5.8 PROFIBUS DP interface (X2, X3)
S7-400H
System Manual, 03/2012, A5E00267695-11
71
5.8
PROFIBUS DP interface (X2, X3)
Connectable devices
The PROFIBUS DP interface can be used to set up a PROFIBUS master system, or to
connect PROFIBUS I/O devices.
You can connect redundant I/O to the PROFIBUS DP interface.
You can connect any standard-compliant DP slaves to the PROFIBUS DP interface.
Here, the CPU represents the DP master, and is connected to the passive slave stations or,
in stand-alone mode, to other DP masters via the PROFIBUS DP fieldbus.
Various compatible devices take the 24 V supply from the interface. This voltage provided at
the PROFIBUS DP interface is non-isolated.
Connectors
Always use bus connectors for PROFIBUS DP and PROFIBUS cables to connect devices to
the PROFIBUS DP interface (
refer to the Installation Manual).
Redundant mode
In redundant mode, the PROFIBUS DP interfaces have the same parameters.
5.9
PROFINET interface (X5)
Assigning an IP address
You have the following options of assigning an IP address to the Ethernet interface:
●
By editing the CPU properties in HW Config. Download the modified configuration to the
CPU.
You can also set up the IP address parameters and the station name (NameOfStation, NoS)
locally without having to modify the configuration data.
●
Using the "PLC -> Edit Ethernet Node" command in SIMATIC Manager.
These local settings are always possible, regardless of whether the PROFINET IO interface
is set up as intelligent device or IO controller in the parameters.
Devices which can be connected via PROFINET (PN)
●
Programming device/PC with Ethernet adapter and TCP protocol
●
Active network components, e.g. Scalance X200
●
S7-300/S7-400, e.g. CPU 417-5H PN/DP
●
PROFINET IO devices, e.g. IM 153-4 PN in an ET 200M
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...