Failure and replacement of components during operation
16.2 Failure and replacement of components during operation
S7-400H
System Manual, 03/2012, A5E00267695-11
267
Step
What has to be done?
How does the system react?
6
Perform a CPU memory reset on the
replaced CPU.
–
7
Start the replaced CPU (for example, STOP-
RUN or Start using the PG).
The CPU performs an automatic LINK-
UP and UPDATE.
The CPU changes to RUN and operates
as the reserve CPU.
Starting situation for replacement of the load memory
Failure
How does the system react?
The S7-400H is in redundant system mode and a
load memory access error occurs.
The relevant CPU changes to STOP and
requests a memory reset.
The partner CPU switches to single mode.
Procedure
Follow the steps below to replace the load memory:
Step
What has to be done?
How does the system react?
1
Replace the memory card on the stopped
CPU.
–
2
Perform a memory reset on the CPU with the
replaced memory card.
–
3
Start the CPU.
The CPU performs an automatic LINK-
UP and UPDATE.
The CPU changes to RUN and operates
as the reserve CPU.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...