Communication
14.5 Communication via S7 connections
S7-400H
240
System Manual, 03/2012, A5E00267695-11
14.5.2
Communication via redundant S7 connections
Availability
Availability can be enhanced by using a redundant plant bus and two separate CPs in a
standard system.
Redundant communication can also be operated with standard connections. For this two
separate S7 connections must be configured in the program in order to implement
connection redundancy. In the user program, both connections require the implementation of
monitoring functions in order to allow the detection of failures and to change over to the
standby connection.
The following figure shows such a configuration.
&38
D
&38
E
&3
D
&3
E
&3
E
&38D
&38D
&3D
&3D
&3E
&3E
&38E
%XV
%XV
)DXOWWROHUDQW
)DXOWWROHUDQW
6WDQGDUGV\VWHP
6WDQGDUGV\VWHP
%ORFNGLDJUDP
%XV
%XV
Figure 14-10 Example of redundancy with fault-tolerant systems and a redundant bus system with
redundant standard connections
Response to failure
Double errors in the fault-tolerant system (i.e. CPUa1 and CPa 2) or in the standard system
(CPb1 and CPb2), and single errors in the standard system (CPUb1) lead to a total failure of
communication between the systems involved (see previous figure).
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...