Assembly of a CPU 41x–H
5.10 Overview of the parameters for the S7-400H CPUs
S7-400H
System Manual, 03/2012, A5E00267695-11
75
●
Security levels
●
Fault tolerance parameters
Note
16 bit memory bytes and 8 counters are set by default in retentive memory, i.e., they are
not deleted at a CPU restart.
Parameter assignment tool
You can set the individual CPU parameters using "HW Config" in STEP 7.
Note
If you modify the parameters listed below, the operating system initializes the following:
Size of the process input image
Size of the process output image
Size of the local data
Number of diagnostic buffer entries
Communication resources
This involves the following initialization actions:
Data blocks are initialized with the load values
Bit memories, timers, counters, inputs and outputs are deleted, regardless of their
retentivity setting (0).
DBs generated by SFC will be deleted
Permanently configured, basic communication connections are shut down
All run levels are initialized.
Further settings
●
The rack number of a fault-tolerant CPU, 0 or 1
Use the selector switch on the rear panel of the CPU to change the rack number.
●
The operating mode of a fault-tolerant CPU: Stand-alone or redundant mode
For information on how to change the operating mode of a fault-tolerant CPU, refer to
Appendix Stand-alone operation (Page 447).
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...