Characteristic values of redundant automation systems
A.1 Basic concepts
S7-400H
438
System Manual, 03/2012, A5E00267695-11
Common Cause Failure (CCF)
The Common Cause Failure (CCF) is an error which is caused by one or more events which
also lead to an error state on two or more separate channels or components in a system. A
CCF leads to a system failure.
The CCF may be caused by one of the following factors:
●
Temperature
●
Humidity
●
Corrosion
●
Vibration and shock
●
Electromagnetic interference
●
Electrostatic discharge
●
RF interference
●
Unexpected sequence of events
●
Operating errors
The CCF factor defines the ratio between the probability of the occurrence of a CCF and the
probability of the occurrence of any other error.
Typical CCF factors range from 2% to 0.2% in a system with identical components, and
between 1% and 0.1% in a system containing different components.
Within the range stipulated in IEC 61508, a CCF factor between 0.02% and 5% is used to
calculate the MTBF.
(UURURQFKDQQHO
(UURURQFKDQQHO
&&)DIIHFWVERWK
FKDQQHOV
Figure A-3
Common Cause Failure (CCF)
Reliability of an S7-400H
The use of redundant modules prolongs the system MTBF by a large factor. The integrated
high-grade self-test and the test/message functions of the S7-400H CPUs enable the
detection and localization of virtually all errors. The calculated diagnostic coverage is around
90%.
The reliability in stand-alone mode is described by the corresponding failure rate. The failure
rate for all S7 components is calculated according to the SN29500 standard.
The reliability in redundant mode is described by the failure rate of the components involved.
This is termed "MTBF" below. Those combinations of failed components which cause a
system failure are described and calculated using Markov models. Calculations of the
system MTBF take account of the diagnostic coverage and the common cause factor.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...