S7-400 cycle and response times
19.2 Calculating the cycle time
S7-400H
System Manual, 03/2012, A5E00267695-11
361
Table 19- 5 Portion of the process image transfer time, CPU 416-5H
Portion
CPU 416–5H
stand-alone mode
CPU 416–5H
redundant
K
Base load
5 µs
6 µs
A
*)
In the central controller
Read/write byte/word/double word
8 µs
20 µs
B
*)
In the expansion unit with local link
Read/write byte/word/double word
22 µs
35 µs
C
*)**)
In the expansion unit with remote link
Read/write byte/word/double word
46 µs
57 µs
D1
In the DP area for the integrated DP interface
Read byte/word/double word
0.45 µs
15 µs
D2
***)
In the DP area for the external DP interfaces
Read/write byte/word/double word
5.1 µs
20 µs
E1
Consistent data in the process image for the integrated DP
interface
Read/write data
12 µs
35 µs
E2
Consistent data in the process image for the external DP
interface (CP 443–5 extended)
Read
write
127 µs
60 µs
141 µs
80 µs
F
In the PNIO area for the integrated PROFINET interface
Read/write for each byte/word/double word
2.5 µs
20 µs
G
Per submodule with 32 bytes of consistent data for the
integrated PROFINET interface
12 µs
35 µs
*)
In the case of I/O inserted into the central controller or expansion device,
the specified value contains the execution time of the I/O module
The module data is updated with the minimum number of accesses.
(example: 8 bytes result in 2 double word accesses; 16 bytes in 4 double word accesses.)
**)
Measured with IM460-3 and IM461-3 at a link length of 100 m
***)
Measured with modules with 1 byte of user data, e.g. DI 16.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...