Failure and replacement of components during operation
16.3 Failure and replacement of components of the distributed I/Os
S7-400H
System Manual, 03/2012, A5E00267695-11
277
Procedure
Proceed as follows to replace a PROFIBUS DP master:
Step
What has to be done?
How does the system react?
1
Turn off the power supply of the central
rack.
The fault-tolerant system switches to single
mode.
2
Unplug the Profibus DP cable of the
affected DP master module.
–
3
Replace the module.
–
4
Plug the Profibus DP back in.
–
5
Turn on the power supply of the central
rack.
The CPU performs an automatic LINK-
UP and UPDATE.
The CPU changes to RUN and operates
as the reserve CPU.
16.3.2
Failure and replacement of a redundant PROFIBUS DP interface module
Starting situation
Failure
How does the system react?
The S7-400H is in redundant system mode and a
PROFIBUS DP interface module (IM 153–2, IM
157) fails.
Both CPUs report the event in the diagnostic
buffer and via OB 70.
Replacement procedure
Proceed as follows to replace the PROFIBUS DP interface module:
Step
What has to be done?
How does the system react?
1
Turn off the supply for the affected DP
interface module.
–
2
Remove the bus connector.
–
3
Insert the new PROFIBUS DP interface
module and turn the power supply back on.
–
4
Plug the bus connector back in.
The CPUs process the I/O redundancy
error OB 70 (outgoing event)
synchronized with each other.
Redundant access to the station by the
system is now possible again.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...