PROFINET
8.4 System status lists for PROFINET IO
S7-400H
System Manual, 03/2012, A5E00267695-11
101
8.4
System status lists for PROFINET IO
Introduction
The CPU makes certain information available and stores this information in the "System
status list".
The system status list describes the current status of the automation system. It provides an
overview of the configuration, the current parameter assignment, the current statuses and
sequences in the CPU, and the assigned modules.
The system status list data can only be read, but not be changed. The system status list is a
virtual list that is compiled only on request.
From a system status list you receive the following information via the PROFINET IO
system:
●
System data
●
Module status information in the CPU
●
Diagnostic data from a module
●
Diagnostic buffer
Compatibility of the new system status lists
For PROFINET IO, some new system status lists were created, among other things,
because larger configurations are now possible with PROFINET.
You can also use these new system status lists with PROFIBUS.
You can continue to use a known PROFIBUS system status list that is also supported by
PROFINET. If you use a system status list in PROFINET that PROFINET does not support,
an error code is returned in RET_VAL (8083: Index wrong or not permitted).
Comparison of the system status lists of PROFINET IO and PROFIBUS DP
Table 8- 4
Comparison of the system status lists of PROFINET IO and PROFIBUS DP
SSL-ID
PROFINET IO
PROFIBUS DP
Applicability
W#16#0591
Yes
Parameter adr1 changed
Yes
Module status information for the
interfaces of a module
W#16#0C91
Yes, internal interface
Parameter adr1/adr2 and
set/actual type identifier
changed
No, external interface
Yes, internal interface
No, external interface
Module status information of a module in
a central configuration or at an integrated
DP or PROFIBUS interface, or at an
integrated DP interface using the logical
address of the module.
W#16#4C91
No
No, internal interface
Yes, external interface
Module status information of a module
attached to an external DP or
PROFIBUS interface using the start
address.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...