S7-400 cycle and response times
19.2 Calculating the cycle time
S7-400H
System Manual, 03/2012, A5E00267695-11
359
Process image update
The table below shows the time a CPU requires to update the process image (process
image transfer time). The specified times only represent "ideal values", and may be
extended accordingly by any interrupts or communication of the CPU.
Calculation of the transfer time for process image update:
K+ portion in the central controller (from row A in the following table)
+ portion in the expansion device with local connection (from row B)
+ portion in the expansion device with remote connection (from row C)
+ portion via integrated DP interface (from row D1)
+ portion via external DP interface (from row D2)
portion of consistent data via integrated DP interface (from row E1)
+ portion of consistent data via external DP interface (from row E2)
+ portion in PN/IO area for the integrated PROFINET interface (from row F)
+ portion for each submodule with 32 byte of consistent data for the integrated PROFINET
interface (from row G)
= Transfer time for process image update
The tables below show the various portions of the transfer time for a process image update
(process image transfer time). The specified times only represent "ideal values", and may be
extended accordingly by any interrupts or communication of the CPU.
Table 19- 3 Portion of the process image transfer time, CPU 412-5H
Portion
CPU 412–5H
stand-alone mode
CPU 412–5H
redundant
K
Base load
10 µs
13 µs
A
*)
In the central controller
Read/write byte/word/double word
9.5 µs
35 µs
B
*)
In the expansion unit with local link
Read/write byte/word/double word
24 µs
50 µs
C
*)**)
In the expansion unit with remote link
Read/write byte/word/double word
48 µs
75 µs
D1
In the DP area for the integrated DP interface
Read byte/word/double word
0.75 µs
35 µs
D2
***)
In the DP area for the external DP interfaces
Read/write byte/word/double word
6.0 µs
40 µs
E1
Consistent data in the process image for the integrated DP
interface
Read/write data
28 µs
70 µs
E2
Consistent data in the process image for the external DP
interface (CP 443–5 extended)
Read
write
250 µs
70 µs
300 µs
115 µs
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...