System modifications during operation
17.6 Removing components in STEP 7
S7-400H
318
System Manual, 03/2012, A5E00267695-11
17.6.6
STEP 7, step 6: Transition to redundant system mode
Starting situation
The fault-tolerant system is operating with the new (restricted) hardware configuration in
single mode.
Procedure
1.
In SIMATIC Manager, select a CPU of the fault-tolerant system, then choose "PLC >
Operating Mode" from the menu.
2.
From the "Operating Mode" dialog box, select the reserve CPU, then click "Warm
Restart".
Result
The reserve CPU links up and is updated. The fault-tolerant system is operating in redundant
system mode.
Reaction of the I/O
Type of I/O
One-sided I/O of reserve CPU One-sided I/O of master CPU
Switched I/O
I/O modules to be
removed
1)
are no longer addressed by the CPU.
I/O modules still
present
are given new parameter
settings
2)
and updated by the
CPU.
continue operation without interruption.
DP stations to be
removed
as for I/O modules to be removed (see above)
1) No longer included in the hardware configuration, but still plugged in
2) Central modules are first reset. Output modules briefly output 0 during this time (instead of the configured substitute or
hold values).
Reaction to monitoring timeout
If one of the monitored times exceeds the configured maximum, the update is canceled. The
fault-tolerant system remains in single mode with the previous master CPU and, assuming
certain conditions are met, attempts the link-up and update later. For additional information,
refer to section Time monitoring (Page 155).
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...