System modifications during operation
17.5 Adding components in STEP 7
S7-400H
System Manual, 03/2012, A5E00267695-11
309
17.5.8
STEP 7, step 8: Editing and downloading the user program
Starting situation
The fault-tolerant system is operating with the new hardware configuration in redundant
system mode.
Restrictions
CAUTION
Any attempts to modify the structure of an FB interface or the instance data of an FB in
redundant system mode will lead to stop system mode (both CPUs in STOP mode).
Procedure
1.
Adapt the program to the new hardware configuration.
You can add, edit or remove OBs, FBs, FCs and DBs.
2.
Download only the program changes to the target system.
3.
Configure the interconnections for the new CPs on both communication partners and
download them to the target system.
NOTICE
Until an FC is called the first time, the value of its output is undefined. This must be
taken into account in the interconnection of the FC outputs.
Result
The fault-tolerant system processes the entire system hardware with the new user program
in redundant system mode.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...