Using I/Os in S7–400H
13.5 Other options for connecting redundant I/Os
S7-400H
System Manual, 03/2012, A5E00267695-11
207
13.5
Other options for connecting redundant I/Os
Redundant I/O at user level
If you cannot use the redundant I/O supported by your system (section Connecting
redundant I/O to the PROFIBUS DP interface (Page 177)), for example because the relevant
module may not be listed among the supported components, you can implement the use of
redundant I/O at the user level.
Configurations
The following redundant I/O configurations are supported:
1.
Redundant configuration with one-sided central and/or distributed I/O.
For this purpose, one signal module each is inserted into the CPU 0 and CPU 1
subsystems.
2.
Redundant configuration with switched I/O
One signal module each is inserted into two ET 200M distributed I/O devices with active
backplane bus.
5HGXQGDQWRQHVLGHG,2
5HGXQGDQWVZLWFKHG,2
Figure 13-13 Redundant one-sided and switched I/O
NOTICE
When using redundant I/O, you may need to add time to the calculated monitoring times;
see section Determining the monitoring times (Page 159)
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...