System and operating states of the S7–400H
11.2 System states of the S7–400H
S7-400H
124
System Manual, 03/2012, A5E00267695-11
11.2
System states of the S7–400H
11.2.1
The system states of the S7-400H
The system states of the S7-400H result from the operating states of the two CPUs. The
term "system state" is used as a simplified term which identifies the concurrent operating
states of the two CPUs.
Example: Instead of "the master CPU is in RUN and the reserve CPU is in LINK-UP mode"
we say "the S7-400H system is in link-up mode".
Overview of system states
The table below provides an overview of the possible states of the S7-400H system.
Table 11- 1 Overview of S7-400H system states
System states of the S7–400H
Operating states of the two CPUs
Master
Reserve
Stop
STOP
STOP, power off, DEFECTIVE
Start-up
STARTUP
STOP, power off, DEFECTIVE, no
synchronization
Single mode
RUN
STOP, ERROR-SEARCH, power off,
DEFECTIVE, no synchronization
Link-up
RUN
STARTUP, LINK-UP
Update
RUN
UPDATE
Redundant
RUN
RUN
Hold
HOLD
STOP, ERROR-SEARCH, power off,
DEFECTIVE, no synchronization
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...