Communication
14.1 Communication services
S7-400H
216
System Manual, 03/2012, A5E00267695-11
S7 communication services provide the following options:
●
During system configuration, you configure the connections used by the
S7 communication. These connections remain configured until you download a new
configuration.
●
You can establish several connections to the same partner. The number of
communication partners accessible at any time is restricted to the number of connection
resources available.
●
You can configure fault-tolerant S7 connections using the integrated PROFINET
interface.
NOTICE
Downloading the connection configuration in RUN
When you load a modified connection configuration during operation, connections which
have been set up which are not affected by changes in the connection configuration
may also be aborted.
S7 communication allows you to transfer a block of up to 64 KB per call to the SFB. An
S7-400 transfers a maximum of 4 tags per block call.
SFBs for S7 Communication
The following SFBs are integrated in the operating system of the S7-400 CPUs:
Table 14- 3 SFBs for S7 Communication
Block
Block name
Brief description
SFB 8
SFB 9
USEND
URCV
Send data to a remote partner SFB with the type "URCV"
Receive asynchronous data from a remote partner SFB with the type "USEND"
SFB 12
SFB 13
BSEND
BRCV
Send data to a remote partner SFB with the type "BRCV"
Receive asynchronous data from a remote partner SFB with the type "BSEND"
With this data transfer, a larger amount of data can be transported between the communication
partners than is possible with all other communications SFBs for the configured S7
connections.
SFB 14
GET
Read data from a remote CPU
SFB 15
PUT
Write data to a remote CPU
SFB 16
Send data via a CP 441 to a printer
SFB 19
START
Carry out a reboot (warm restart) or cold restart in a remote station
SFB 20
STOP
Set a remote station to STOP state
SFB 21
RESUME
Carry out a hot restart in a remote station
SFB 22
STATUS
Query the device status of a remote partner
SFB 23
USTATUS
Uncoordinated receiving of a remote device status
Integration into STEP 7
S7 communication offers communication functions through configured S7 connections. You
use STEP 7 to configure the connections.
S7 connections with an S7-400 are established when the connection data is downloaded.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...