Getting Started
4.4 Examples of the response of the fault-tolerant system to faults
S7-400H
44
System Manual, 03/2012, A5E00267695-11
4.4
Examples of the response of the fault-tolerant system to faults
Example 1: Failure of a CPU or power supply module
Initial situation: The S7-400H is in redundant system mode.
1.
Simulate a CPU0 failure by turning off the power supply.
Result: The LEDs REDF, IFM1F and IFM2F light up on CPU1. CPU1 goes into single
mode and continues to process the user program.
2.
Turn the power supply back on.
Result:
–
CPU0 performs an automatic LINK-UP and UPDATE.
–
CPU0 changes to RUN, and now operates as reserve CPU.
–
The S7-400H is now in redundant system mode.
Example 2: Failure of a fiber-optic cable
Initial situation: The S7-400H is in redundant system mode. The mode selector switch of
each CPU is set to RUN.
1.
Disconnect one of the fiber-optic cables.
Result: The LEDs REDF and IFM1F or IFM2F (depending on which fiber-optic cable was
disconnected) now light up on both CPUs. The reserve CPU changes to ERROR-
SEARCH mode. The other CPU remains master and continues operation in single mode.
2.
Reconnect the fiber-optic cable.
Result: The reserve CPU performs starts a LINK-UP and UPDATE. The S7–400H
resumes redundant system mode.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...