System modifications during operation
17.4 Removing components in PCS 7
S7-400H
302
System Manual, 03/2012, A5E00267695-11
17.4.8
Removing interface modules in PCS 7
Always switch off the power before you remove the IM460 and IM461 interface modules,
external CP 443-5 Extended DP master interface module, and their connecting cables.
Always switch off power to an entire subsystem. To ensure that this does not influence the
process, always set the subsystem to STOP before you do so.
Procedure
1.
Change the hardware configuration offline (see section PCS 7, step 1: Editing the
hardware configuration offline (Page 296))
2.
Modify and download the user program (see section PCS 7, step 2: Editing and
downloading the user program (Page 297))
3.
Stop the reserve CPU (see section PCS 7, step 3: Stopping the reserve CPU (Page 298))
4.
Download the new hardware configuration to the reserve CPU (see section PCS 7, step
4: Downloading a new hardware configuration to the reserve CPU (Page 298))
5.
Follow the steps below to remove an interface module from the subsystem of the reserve
CPU:
–
Switch off the power supply of the reserve subsystem.
–
Remove an IM460 from the central unit.
or
–
Remove an expansion unit from an existing chain.
or
–
Remove an external DP master interface module.
–
Switch on the power supply of the reserve subsystem again.
6.
Switch to CPU with altered configuration (see section PCS 7, step 5: Switching to CPU
with modified configuration (Page 299))
7.
Proceed as follows to remove an interface module from the subsystem of the original
master CPU (currently in STOP mode):
–
Switch off the power supply of the reserve subsystem.
–
Remove an IM460 from the central unit.
or
–
Remove an expansion unit from an existing chain.
or
–
Remove an external DP master interface module.
–
Switch on the power supply of the reserve subsystem again.
8.
Change to redundant system mode (see section PCS 7, step 6: Transition to redundant
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...