Link-up and update
12.4 Time monitoring
S7-400H
156
System Manual, 03/2012, A5E00267695-11
●
Maximum inhibit time for priority classes > 15
–
Inhibit time for priority classes > 15: The time span during an update during which no
OBs (and thus no user program) are executed nor any I/O updates are implemented.
–
Maximum inhibit time for priority classes > 15: The maximum permissible inhibit time
for priority classes > 15 configured by the user.
●
Minimum I/O retention time:
This represents the interval between copying of the outputs from the master CPU to the
standby CPU, and the time of the transition to the redundant system mode or
master/standby changeover (time at which the previous master CPU goes into STOP and
the new master CPU goes into RUN). Both CPUs control the outputs within this period, in
order to prevent the I/O from going down when the system performs an update with
master/standby changeover.
The minimum I/O retention time is of particular importance when updating with
master/standby changeover. If you set the minimum I/O retention time to 0, the outputs
could possibly shut down when you modify the system during operation.
The monitoring start times are indicated in the highlighted boxes in Figure 12-2. These times
expire when the system enters the redundant system mode or when there is a
master/standby changeover, i.e. on the transition of the new master to RUN when the update
is completed.
The figure below provides an overview of the relevant update times.
8SGDWH
0LQLPXP,2UHWHQWLRQWLPH
,QKLELWWLPHIRUSULRULW\FODVVHV!
&RPPXQLFDWLRQGHOD\
&\FOHWLPHH[WHQVLRQ
W
W
W
W
W
W
W(QGRIFXUUHQW2%VXSWRSULRULW\FODVV
W6WRSDOOFRPPXQLFDWLRQIXQFWLRQV
W(QGRIZDWFKGRJLQWHUUXSW2%ZLWKVSHFLDOKDQGOLQJ
W(QGRIFRS\LQJRIRXWSXWVWRWKHVWDQGE\&38
W5HGXQGDQWV\VWHPVWDWXVRUPDVWHUVWDQGE\FKDQJHRYHU
Figure 12-4 Meanings of the times relevant for updates
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...