System and operating states of the S7–400H
11.3 The operating states of the CPUs
S7-400H
System Manual, 03/2012, A5E00267695-11
135
11.3.5
HOLD mode
Except for the additions described below, the behavior of the S7-400H CPU in HOLD mode
corresponds to that of a standard S7-400 CPU.
The HOLD mode has an exceptional role, as it is used only for test purposes.
When is the HOLD mode possible?
A transition to HOLD is only available during STARTUP and in RUN in single mode.
Properties
●
Link-up and update operations are not available while the fault-tolerant CPU is in HOLD
mode; the reserve CPU remains in STOP and outputs a diagnostics message.
●
It is not possible to set breakpoints when the fault-tolerant system is in redundant system
mode.
11.3.6
ERROR-SEARCH mode
The ERROR-SEARCH mode can only be adopted from the redundant system mode. During
troubleshooting, the redundant system mode is exited, the other CPU can become master
and continue to work in standalone mode.
Note
If the master CPU changes to STOP during troubleshooting, the troubleshooting is continued
on the standby CPU. However, once troubleshooting is completed, the standby CPU does
not start up again.
The following events will trigger ERROR-SEARCH mode:
1.
If a one-sided call of OB 121 (on only one CPU) occurs in redundant mode, the CPU
assumes a hardware fault and enters ERROR-SEARCH mode. The partner CPU
assumes master mode as required, and continues operation in standalone mode.
2.
If a checksum error occurs on only one CPU in redundant mode, that CPU enters
ERROR-SEARCH mode. The partner CPU assumes master mode as required, and
continues operation in standalone mode.
3.
If a RAM/POI comparison error is detected in redundant mode, the standby CPU enters
ERROR-SEARCH mode (default response), and the master CPU continues operation in
standalone mode.
The response to RAM/POI comparison errors can be modified in the configuration (for
example, the standby CPU goes into STOP).
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...