Link-up and update
12.4 Time monitoring
S7-400H
System Manual, 03/2012, A5E00267695-11
167
12.4.4
Influences on time response
The period during which no I/O updates take place is primarily determined by the following
influencing factors:
●
The number and size of data blocks modified during the update
●
The number of instances of SFBs in S7 communication and of SFBs for generating block-
specific messages
●
System modifications during operation
●
Settings by means of dynamic quantity structures
●
Expansion of distributed I/Os with PROFIBUS DP (a lower baud rate and higher number
of slaves increases the time it takes for I/O updates).
●
Expansion of distributed I/Os with PROFINET IO (a higher update time and higher
number of devices increases the time it takes for I/O updates).
In the worst case, this period is extended by the following amounts:
●
Maximum cyclic interrupt used
●
Duration of all cyclic interrupt OBs
●
Duration of high-priority interrupt OBs executed until the start of interrupt delays
Explicit delay of the update
Delay the update using SFC 90 "H_CTRL", and re-enable it only when the system state
shows less communication or interrupt load.
CAUTION
The update delay increases the time of standalone mode operation of the fault-tolerant
system.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...