LIEBERT® RPC2™
COMMUNICATIONS MODULE
Quick Installation Guide
SL20842_Rev3/590-1771-501A
1
The RPC2™ Communications
Module provides network and
environmental sensor connectivity
for the Liebert™ rack PDU family of
products. It provides Ethernet and
serial communication interfaces as
well as the ability to connect up to
four rack PDUs in an array, sharing
one IP address. Devices powered
by a rack PDU can be remotely
controlled and monitored through
the RPC2’s various interfaces. The
RPC2 also supports the connection
of an optional external LCD display.
Please see the RPC2
Communications Module Installer/
User Guide for further information.
The following are instructions to
install and configure the
communications module in the
rack PDU.
Setting up the RPC2
Communications Module
The RPC2 can be accessed either
via DHCP (factory default) or static
IP boot mode through the network
(LAN) port. To find the DHCP IP
address, see the MPH2™ Rack PDU
Installer/User Guide. To configure
the static IP boot mode, the
network settings must be changed
via the link port as follows.
1. Locating the
communication card bay
Find the communication card
bay on the rack PDU. It may
have a removable cover.
2. Inserting the RPC2
communications module
Insert the RPC2
communications module into
the card bay and secure it by
tightening the captive
thumbscrews.
NOTE:
The RPC2 factory
default boot mode is DHCP for
the LAN port, so no changes
are necessary.
3. Connecting a laptop
Connect a CAT5 Ethernet cable
(not included) from a laptop to
the RPC2’s link port.
NOTE:
Do not connect the link
port to your network. The
RPC2’s link port should only be
used for local configuration or
linking together a Rack PDU
Array™.
4. Configuring the RPC2
through the link port
To establish communication
through the link port, first
configure the laptop’s Ethernet
adaptor with the following
settings:
IP Address: 192.168.1.9
Subnet mask: 255.255.255.252
Default gateway: 192.168.1.1
5. Entering the link port IP
address
Open a web browser and enter
192.168.1.10. When prompted,
enter
admin
for both the login
and the password and click the
Login icon or press
Enter
.
6. Configuring the network
Click the
System
tab and click
Settings - Network
in the
navigation tree. Click the Edit
icon in the right pane. Select
Static
for the IPV4 Boot Mode
and enter the IP address,
subnet mask and default
gateway in the proper fields.
See your network administrator
for these settings.
RPC2™ Communications Module Installation
Link
Network
Display
Sensor
Serial
USB Micro-AB