Consistent data
9.3 Consistent reading and writing of data from and to DP standard slaves/IO devices
S7-400H
116
System Manual, 03/2012, A5E00267695-11
Example:
The example of the process image partition 3 "PIP 3" below shows a possible configuration
in HW Config. Requirement: The process image was previously updated by means of
SFC 26/27 call, or the update of the process image was linked to an OB.
●
PIP 3 at output: Those 50 bytes are stored consistently in process image partition 3 (drop
down list box "Consistent over > Total length"), and can thus be read by means of
standard "Load input xy" commands.
●
Selecting "Process image -> ---" under Input in the drop down list box means: no storage
in a process image. You must work with the system functions SFC14/15.
Figure 9-1
Properties - DP slave
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...