System modifications during operation
17.9 Re-parameterization of a module
S7-400H
334
System Manual, 03/2012, A5E00267695-11
17.9
Re-parameterization of a module
17.9.1
Re-parameterization of a module
Refer to the information text in the "Hardware Catalog" window to determine which modules
(signal modules and function modules) can be reconfigured during ongoing operation. The
specific reactions of individual modules are described in the respective technical
documentation.
NOTICE
If you edit any protected parameters, the system will reject any attempt to changeover to
the CPU containing those modified parameters. The event W#16#5966 is written to the
diagnostic buffer. and you will then have to restore the wrongly changed parameters in the
parameter configuration to their last valid values.
The selected new values must match the current and the planned user program.
Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
To edit the parameters of modules in a fault-tolerant system, perform the steps outlined
below. Details of each step are described in a subsection.
Step
What to do?
See section
1
Editing parameters offline
Step 1: Editing parameters offline (Page 335)
2
Stopping the reserve CPU
Step 2: Stopping the reserve CPU (Page 336)
3
Downloading modified CPU parameters to the reserve
CPU
Step 3: Downloading a new hardware
configuration to the reserve CPU (Page 336)
4
Switching to CPU with modified configuration
Step 4: Switching to CPU with modified
5
Transition to redundant system mode
Step 5: Transition to redundant system mode
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...