Special functions of a CPU 41x-H
6.4 Updating the firmware without a memory card
S7-400H
System Manual, 03/2012, A5E00267695-11
83
6.4
Updating the firmware without a memory card
Basic procedure
To update the firmware of a CPU, you will receive several files (*.UPD) containing the
current firmware. Download these files to the CPU. You do not need a memory card to
perform an online update. However, it is still possible to update the firmware using a memory
card.
Requirement
The CPU whose firmware you want to update must be accessible online, e.g. via
PROFIBUS, MPI, or Industrial Ethernet. The files containing the current firmware versions
must be available in the programming device/PC file system. A folder may contain only the
files of one firmware version. If security level 2 or 3 is set for the CPU, you require the
password to update the firmware.
Note
You can update the firmware of the fault-tolerant CPUs via Industrial Ethernet. Updating the
firmware over a MPI can take a long time if the transfer rate is low (e.g. approximately 10
minutes at 187.5 Kbit/s).
Procedure in HW Config
Proceed as follows to update the firmware of a CPU:
1.
Open the station containing the CPU you want to update in HW Config.
2.
Select the CPU.
3.
Select the "PLC -> Update Firmware" menu command.
4.
In the "Update Firmware" dialog, select the path to the firmware update files (*.UPD)
using the "Browse" button.
After you have selected a file, the information in the bottom boxes of the "Update
Firmware" dialog box indicate the modules for which the file is suitable and from which
firmware version.
5.
Click on "Run".
STEP 7 verifies that the selected file can be interpreted by the CPU and then downloads the
file to the CPU. If this requires changing the operating state of the CPU, you will be prompted
to do this in the relevant dialog boxes.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...