System modifications during operation
17.9 Re-parameterization of a module
S7-400H
System Manual, 03/2012, A5E00267695-11
335
Note
After changing the hardware configuration, download takes place practically automatically.
This means that you no longer need to perform the steps described in sections Step 2:
Stopping the reserve CPU (Page 336) to Step 5: Transition to redundant system mode
(Page 339). The system behavior remains as described.
You will find more information in the HW Config online help "Download to module ->
Download station configuration in RUN mode".
17.9.2
Step 1: Editing parameters offline
Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
1.
Edit the module parameters offline in HW Config.
2.
Compile the new hardware configuration, but do not load it into the target system just yet.
Result
The modified hardware configuration is in the PG/ES. The target system continues operation
with the old configuration in redundant system mode.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...