S7-400 cycle and response times
19.8 Interrupt response time
S7-400H
System Manual, 03/2012, A5E00267695-11
379
19.8
Interrupt response time
Definition of interrupt response time
The interrupt response time is the time from the first occurrence of an interrupt signal to the
call of the first instruction in the interrupt OB.
General rule: Higher priority interrupts are handled first. This means the interrupt response
time is increased by the program execution time of the higher-priority interrupt OBs, and by
previous interrupt OBs of the same priority which have not yet been processed (queue).
Note that any update of the standby CPU extends the interrupt response time.
Calculating the interrupt response time
Minimum interrupt response time of the CPU
+ minimum interrupt response time of the
signal modules
+ PROFIBUS DP cycle time on PROFINET
= Shortest interrupt response time
Minimum interrupt response time of the CPU
+ maximum interrupt response time of the
signal modules
+ 2 * cycle time on PROFIBUS DP or PROFINET
= Longest interrupt response time
Process and diagnostic interrupt response times of the CPUs
Table 19- 14 Process and interrupt response times; maximum interrupt response time without
communication
CPU
Hardware interrupt response
times
Diagnostic interrupt response
times
min.
max.
min.
max.
412-5H stand-alone mode
190 µs
370 µs
200 µs
390 µs
412–5H redundant
370 µs
850 µs
410 µs
690 µs
414–5H stand-alone mode
140 µs
200 µs
150 µs
330 µs
414–5H redundant
330 µs
620 µs
290 µs
490 µs
416–5H stand-alone mode
90 µs
140 µs
90 µs
200 µs
416–5H redundant
240 µs
500 µs
200 µs
400 µs
417–5H stand-alone mode
80 µs
90 µs
80 µs
90 µs
417–5H redundant
160 µs
310 µs
140 µs
250 µs
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...