Link-up and update
12.4 Time monitoring
S7-400H
System Manual, 03/2012, A5E00267695-11
159
12.4.2
Determining the monitoring times
Calculation using STEP 7 or formulas
STEP 7 automatically calculates the monitoring times listed below for each new
configuration. You can also calculate these times using the formulas and procedures
described below. They are equivalent to the formulas provided in STEP 7.
●
Maximum cycle time extension
●
Maximum communication delay
●
Maximum inhibit time for priority classes
●
Minimum I/O retention time
You can also start automatic calculation of monitoring times with Properties CPU > H
Parameters in HW Config.
Monitoring time accuracy
Note
The monitoring times determined by STEP 7 or by using formulas merely represent
recommended values.
These times are based on a fault-tolerant system with two communication peers and an
average communication load.
Your system profile may differ considerably from those scenarios, therefore the following
rules must be observed.
●
The cycle time extension factor may increase sharply at a high communication load.
●
Any modification of the system in operation may lead to a significant increase in cycle
times.
●
Any increase in the number of programs executed in priority classes > 15 (in particular
processing of communication blocks) automatically increases the communication delay
and cycle time extension.
●
You can even undercut the calculated monitoring times in small plants with high-
performance requirements.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...