Using I/Os in S7–400H
13.4 Connecting redundant I/O to the PROFIBUS DP interface
S7-400H
System Manual, 03/2012, A5E00267695-11
187
13.4.1
Signal modules for redundancy
Signal modules as redundant I/O
The signal modules listed below can be used as redundant I/O. Refer to the latest
information about the use of modules available in the readme file and in the SIMATIC FAQ at
http://www.siemens.com/automation/service&support under the keyword "Redundant I/O".
Take into account that you can only use modules of the same product version and same
firmware version as redundant pairs.
Table 13- 3 Signal modules for redundancy
Library V5.x Library V4.x Library V3.x Module
Order number
Central: Redundant DI dual-channel
DI 16xDC 24V interrupt
6ES7 421–7BH0x–0AB0
X
X
Use with non-redundant encoder
This module supports the "wire break" diagnostic function. To implement this
function, make sure that a total current between 2.4 mA and 4.9 mA flows
even at signal state "0" when you use an encoder that is evaluated at two
inputs in parallel.
You achieve this by connecting a resistor via the encoder. Its value depends
on the type of switch and usually ranges between 6800 and 8200 ohms for
contacts.
For BEROS, calculate the resistance based on this formula:
(30 V/(4.9 mA – I_R_Bero) < R < (20 V/(2.4 mA – I_R_Bero)
X
X
DI 32xDC 24V
6ES7 421–1BL0x–0AA0
X
X
DI 32xUC 120V
6ES7 421–1EL00–0AA0
Distributed: Redundant DI dual-channel
X
X
DI16xDC 24 V, interrupt
6ES7 321–7BH00–0AB0
DI16xDC 24 V
6ES7 321–7BH01–0AB0
X
X
X
In the event of an error on one channel, the entire group (2 channels) is
passivated. When using the module with HF index, only the faulty channel is
passivated in the event of a channel error.
Use with non-redundant encoder
This module supports the "wire break" diagnostic function. To implement this
function, make sure that a total current between 2.4 mA and 4.9 mA flows
even at signal state "0" when you use an encoder that is evaluated at two
inputs in parallel.
You achieve this by connecting a resistor via the encoder. Its value depends
on the type of switch and usually ranges between 6800 and 8200 ohms for
contacts.
For BEROS, calculate the resistance based on this formula:
(30 V/(4.9 mA – I_R_Bero) < R < (20 V/(2.4 mA – I_R_Bero)
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...