Link-up and update
12.4 Time monitoring
S7-400H
160
System Manual, 03/2012, A5E00267695-11
Configuration of the monitoring times
When configuring monitoring times, always make allowances for the following dependencies;
conformity is checked by STEP 7:
Max. cycle time extension
> max. communication delay
> (max. inhibit time for priority classes > 15)
> min. I/O retention time
If you have configured different monitoring times in the CPUs and perform a link-up and
update operation with master/standby changeover, the system always applies the higher of
the two values.
Calculating the minimum I/O retention time (T
PH
)
The following applies to the calculation of the minimum I/O retention time:
●
With central I/O: T
PH
= 30 ms
●
For distributed I/O (PROFIBUS DP): T
PH
= 3 x T
TRmax
Where T
TRmax
= maximum target rotation time
of all DP master systems of the fault-tolerant station
●
For distributed I/O (PROFINET IO): T
PH
= T
wd_max
with T
wd_max
= maximum cyclic interrupt time (product of WD factor and update time) of a
switched device in all IO subsystems of the fault-tolerant station
When using central and distributed I/Os, the resultant minimum I/O retention time is:
T
PH
= MAX (30 ms, 3 x T
TRmax
, T
wd_max
)
The following figure shows the correlation between the minimum I/O retention time and the
maximum inhibit time for priority classes > 15.
0DVWHUFRSLHV
RXWSXWVPV
0LQLPXP,2
UHWHQWLRQWLPH
0D[LPXPLQKLELWWLPHIRU
SULRULW\FODVVHV!
Figure 12-5 Correlation between the minimum I/O retention time and the maximum inhibit time for
priority classes > 15
Note the following condition:
50 ms + minimum I/O retention time ≤
(maximum inhibit time for priority classes > 15)
It follows that a high minimum I/O retention time can determine the maximum inhibit time for
priority classes > 15.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...