Configuring with STEP 7
15.1 Configuring with STEP 7
S7-400H
260
System Manual, 03/2012, A5E00267695-11
15.1.1
Rules for arranging fault-tolerant station components
The following rules have to be complied with for a fault-tolerant station, in addition to the
rules that generally apply to the arrangement of modules in the S7-400:
●
Insert the CPUs into the same slots.
●
Redundantly used external DP master interfaces or communication modules must be
inserted in the same slots in each case.
●
Insert an external DP master interface for redundant DP master systems only into the
CPUs and not into the expansion devices.
●
Redundantly used modules (for example, CPU 417-5H, DP slave interface module IM
153-2) must be identical, i.e. they must have the same order number, the same product
version, and the same firmware version.
Layout rules
●
A fault-tolerant station may contain up to 20 expansion devices.
●
Assign module racks with even numbers only to central rack 0, and racks with odd
numbers only to central rack 1.
●
Modules with communication bus interface can be operated only in racks 0 through 6.
●
Communication-bus capable modules are not permissible in switched I/O.
●
Pay attention to the rack numbers for operation of CPs for fault-tolerant communication in
expansion devices:
The numbers must be directly sequential and begin with the even number, e.g. rack
numbers 2 and 3, but not rack numbers 3 and 4.
●
A rack number is also assigned for DP master no. 9 onwards if the central rack contains
DP master modules. The number of possible expansion racks is reduced as a result.
Compliance with the rules is monitored automatically by STEP 7 and considered accordingly
during configuration.
15.1.2
Configuring hardware
The simplest way of achieving a redundant hardware configuration consists in initially
equipping one rack with all the redundant components, assigning parameters to them and
then copying them.
You can then specify the various addresses (for one-sided I/O only!) and arrange other, non-
redundant modules in individual racks.
Special features in presenting the hardware configuration
In order to enable quick recognition of a redundant DP master system, it is represented by
two parallel DP cables.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...