Example of the calculation of T
P15
In the next steps, we take an existing system configuration and define the maximum
permitted time span of an update, during which the operating system does not execute any
programs or I/O updates.
Assumin g two DP master systems and one IO subsystem are available: DP master
system_1 is connected to the CPU via the MPI/DP interface of the CPU, and DP master
system_2 via an external DP master interface. The IO subsystem is connected via the
integrated Ethernet interface.
1.
Based on the bus parameters in STEP 7:
T
TR_1
= 25 ms
T
TR_2
= 30 ms
T
DP_UM_1
= 100 ms
T
DP_UM_2
= 80 ms
2.
Based on the configuration in STEP 7:
T
max_Akt
= 8 ms
T
PN_UM
= 110 ms
3.
Based on the technical data of the DP slaves used:
T
SLAVE_UM_1
= 30 ms
T
SLAVE_UM_2
= 50 ms
4.
Based on the technical specifications of the PN devices used:
T
Device_UM
= 20 ms
5.
Based on the technological settings of your system:
T
PTO_1
= 1250 ms
T
PTO_2
= 1200 ms
T
PTO_PN
= 1000 ms
6.
Based on the user program:
T
WA
= 300 ms
T
PROG
= 50 ms
7.
Based on the formula [1]:
T
P15
(DP master system_1)
= 1250 ms - (2 x 25 ms + 300 ms + 50 ms + 100 ms + 30 ms) = 720 ms
T
P15
(DP master system_2)
= 1200 ms - (2 x 30 ms + 300 ms + 50 ms + 80 ms + 50 ms) = 660 ms
8.
Based on the formula [1]:
T
P15
(IO subsystem)
= 1200 ms - (2 x 8 ms + 300 ms + 50 ms + 110 ms + 20 ms) = 704 ms
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...