Failure and replacement of components during operation
16.2 Failure and replacement of components during operation
S7-400H
System Manual, 03/2012, A5E00267695-11
275
16.2.6
Failure and replacement of an IM 460 and IM 461 interface module
Starting situation
Failure
How does the system react?
The S7-400H is in redundant system mode and
an interface module fails.
The connected expansion unit is turned off.
Both CPUs report the event in the diagnostic
buffer and via OB 86.
Procedure
Follow the steps below to replace an interface module:
Step
What has to be done?
How does the system react?
1
Turn off the power supply of the central
rack.
The partner CPU switches to single
mode.
2
Turn off the power supply of the expansion
unit in which you want to replace the
interface module.
–
3
Remove the interface module.
–
4
Insert the new interface module and turn
the power supply of the expansion unit
back on.
–
5
Switch the power supply of the central unit
back on and start the CPU.
The CPU performs an automatic LINK-
UP and UPDATE.
The CPU changes to RUN and operates
as the reserve CPU.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...