Using I/Os in S7–400H
13.4 Connecting redundant I/O to the PROFIBUS DP interface
S7-400H
188
System Manual, 03/2012, A5E00267695-11
Library V5.x Library V4.x Library V3.x Module
Order number
DI16xDC 24 V
6ES7 321–1BH02–0AA0
X
X
In some system states, it is possible that an incorrect value of the first module is
read in briefly when the front connector of the second module is removed. This is
prevented by using series diodes like those shown in figure F.1.
DI32xDC 24 V
6ES7 321–1BL00–0AA0
X
X
In some system states, it is possible that an incorrect value of the first module is
read in briefly when the front connector of the second module is removed. This is
prevented by using series diodes like those shown in figure F.2.
X
X
DI 8xAC 120/230V
6ES7 321–1FF01–0AA0
DI 4xNamur [EEx ib]
6ES7 321–7RD00–0AB0
X
X
You cannot use the module for applications in hazardous areas in redundant
mode.
Use with non-redundant encoder
You can only connect 2-wire NAMUR encoders or contact makers.
Equipotential bonding of the encoder circuit should always be at one point
only (preferably encoder negative).
When selecting encoders, compare their properties with the specified input
characteristics. Remember that this function must always be available,
regardless of whether you are using one or two inputs. Example of valid
values for NAMUR encoders: for "0" current > 0.2 mA; for "1" current > 4.2
mA.
DI 16xNamur
6ES7321–7TH00–0AB0
X
X
Use with non-redundant encoder
Equipotential bonding of the encoder circuit should always be at one point
only (preferably encoder negative).
Operate the two redundant modules on a common load power supply.
When selecting encoders, compare their properties with the specified input
characteristics. Remember that this function must always be available,
regardless of whether you are using one or two inputs. Example of valid
values for NAMUR encoders: for "0" current > 0.7 mA; for "1" current > 4.2
mA.
DI 24xDC 24 V
6ES7326–1BK00–0AB0
X
X
F module in standard mode
DI 8xNAMUR [EEx ib]
6ES7326–1RF00–0AB0
X
X
F module in standard mode
Central: Redundant DO dual-channel
DO 32xDC 24V/0.5A
6ES7422–7BL00–0AB0
X
X
A clear evaluation of the diagnostics information "P short-circuit", "M short-
circuit" and wire break is not possible. Deselect these individually in your
configuration.
X
X
DO 16xAC 120/230V/2A
6ES7422–1FH00–0AA0
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...