Using I/Os in S7–400H
13.4 Connecting redundant I/O to the PROFIBUS DP interface
S7-400H
System Manual, 03/2012, A5E00267695-11
205
Depassivation of modules
Passivated modules are depassivated by the following events:
●
When the fault-tolerant system starts up
●
When the fault-tolerant system changes over to "redundant" mode
●
After system modifications during operation
●
If you call FC 451 "RED_DEPA" and at least one redundant channel or module is
passivated.
The depassivation is executed in FB 450 "RED IN" after one of these events has occurred.
Completion of the depassivation of all modules is logged in the diagnostic buffer.
Note
When a redundant module is assigned a process image partition and the corresponding OB
is not available on the CPU, the complete passivation process may take approximately 1
minute.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...