Failure and replacement of components during operation
16.2 Failure and replacement of components during operation
S7-400H
270
System Manual, 03/2012, A5E00267695-11
Step
What has to be done?
How does the system react?
1
Disconnect the module from its peripheral
power supply, if necessary.
2
Disconnect the front connector and wiring.
Call OB 82 if the module concerned is
capable of diagnostic interrupts and
diagnostic interrupts are enabled in the
configuration.
Call OB 122 if you are accessing the
module by direct access
Call OB 85 if you are accessing the
module using the process image
3
Remove the failed module (in RUN mode).
Both CPUs process the swapping
interrupt OB 83 synchronized with each
other.
4
Insert the new module.
Both CPUs process the swapping
interrupt OB 83 synchronized with each
other.
Parameters are assigned automatically
to the module by the CPU concerned
and the module is addressed again.
5
Plug the front connector into the new
module.
Call OB 82 if the module concerned is
capable of diagnostic interrupts and
diagnostic interrupts are enabled in the
configuration.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...