System modifications during operation
17.2 Possible hardware modifications
S7-400H
284
System Manual, 03/2012, A5E00267695-11
What should I consider during system planning?
For switched I/O to be expanded during operation, the following points must be taken into
account already at the system planning stage:
●
In both cables of a redundant DP master system, sufficient numbers of branching points
are to be provided for spur lines or isolating points (spur lines are not permitted for
transmission rates of 12 Mbit/s). These branching points can be spaced or implemented
at any points that can be accessed easily.
●
Both cables must be uniquely identified so that the line which is currently active is not
accidentally cut off. This identification should be visible not only at the end points of a
line, but also at each possible new connection point. Different colored cables are
especially suitable for this.
●
Modular DP slave stations (ET 200M), DP/PA links and Y links must always be installed
with an active backplane bus and fitted with all the bus modules required wherever
possible, because the bus modules cannot be installed and removed during operation.
●
Always terminate both ends of PROFIBUS DP and PROFIBUS PA bus cables using
active bus terminating elements in order to ensure proper termination of the cables while
you are reconfiguring the system.
●
PROFIBUS PA bus systems should be built up using components from the SpliTConnect
product range (see interactive catalog CA01) so that separation of the lines is not
required.
●
Loaded data blocks must not be deleted and created again. In other words, SFC 22
(CREATE_DB) and SFC 23 (DEL_DB) may not be applied to DB numbers occupied by
loaded DBs.
●
Always ensure that the current status of the user program is available as STEP 7 project
in block format at the PG/ES when you modify the system configuration. It is not enough
to upload the user program back from one of the CPUs to the PG/ES or to compile it
again from an STL source.
Modification of the hardware configuration
With a few exceptions, all elements of the configuration can be modified during operation.
Usually configuration changes will also affect the user program.
The following must not be changed by means of system modifications during operation:
●
Certain CPU parameters (for details refer to the relevant subsections)
●
The transmission rate (baud rate) of redundant DP master systems
●
S7 and S7 H connections
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...