Link-up and update
12.5 Special features in link-up and update operations
S7-400H
168
System Manual, 03/2012, A5E00267695-11
12.5
Special features in link-up and update operations
Requirement for input signals during the update
Any process signals read previously are retained and not included in the update. The CPU
only recognizes changes of process signals during the update if the changed signal state
remains after the update is completed.
The CPU does not detect pulses (signal transitions "0 → 1 → 0" or "1 → 0 →1") which are
generated during the update.
You should therefore ensure that the interval between two signal transitions (pulse period) is
always greater than the required update period.
Communication links and functions
Connections on the master CPU are not be shut down. However, associated communication
jobs are not executed during updates. They are queued for execution as soon as one of the
following cases occurs:
●
The update is completed, and the system is in the redundant state.
●
The update and master/reserve changeover are completed, the system is in single mode.
●
The update was canceled (e.g. due to timeout), and the system has returned to single
mode.
An initial call of communication blocks is not possible during the update.
Memory reset request on cancelation of link-up
If the link-up operation is canceled while the content of load memory is being copied from the
master to the reserve CPU, the reserve CPU requests a memory reset. This indicated in the
diagnostic buffer by event ID W#16#6523.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...