Communication
14.1 Communication services
S7-400H
214
System Manual, 03/2012, A5E00267695-11
Connection resources in the S7-400 H
S7-400 H components provide a module-specific number of connection resources.
Availability of connection resources
Table 14- 2 Availability of connection resources
Reserved from the total number for
CPU
Total number of
connection resources
Can be used for
S7 connections
PG communication
OP communication
412-5H PN/DP
48
46
1
1
414-5H PN/DP
64
62
1
1
416-5H PN/DP
96
62
1
1
417-5H PN/DP
120
62
1
1
Free S7 connections can be used for any of the above communication services.
Note
Communication service via the PROFIBUS DP interface
A fixed default timeout of 40 s is specified for communication services using S7 connection
resources. Reliable operation of those communication services at a low baud rate via
PROFIBUS DP interface can be ensured in configurations with a Ttr (Target Rotation Time)
< 20 s.
14.1.2
PG communication
Properties
Programming device communication is used to exchange data between engineering stations
(PG, PC, for example) and SIMATIC modules which are capable of communication. This
service is available for MPI, PROFIBUS and Industrial Ethernet subnets. Routing between
subnets is also supported.
You can use the programming device communication for the following actions:
●
Loading programs and configuration data
●
Performing tests
●
Evaluating diagnostic information
These functions are integrated in the operating system of SIMATIC S7 modules.
A CPU can maintain several simultaneous online connections to one or multiple
programming devices.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...