System modifications during operation
17.4 Removing components in PCS 7
S7-400H
System Manual, 03/2012, A5E00267695-11
301
17.4.7
PCS 7, step 7: Modification of hardware
Starting situation
The fault-tolerant system is operating with the new hardware configuration in redundant
system mode.
Procedure
1.
Disconnect all the sensors and actuators from the components you want to remove.
2.
Unplug modules of the one-sided I/Os that are no longer required from the racks.
3.
Unplug components that are no longer required from the modular DP stations.
4.
Remove DP stations that are no longer required from the DP master systems.
NOTICE
With switched I/O: Always complete all changes on one segment of the redundant DP
master system before you modify the next segment.
Result
The removal of non-configured modules does not influence the user program. The same
applies to removing DP stations.
The fault-tolerant system continues to operate in redundant system mode.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...