Using I/Os in S7–400H
13.4 Connecting redundant I/O to the PROFIBUS DP interface
S7-400H
System Manual, 03/2012, A5E00267695-11
193
Library V5.x Library V4.x Library V3.x Module
Order number
AI 6xTC 16Bit iso, 6ES7331-7PE10-0AB0
6ES7331-7PE10-0AB0
X
X
Notice: These modules must only be used with redundant encoders.
You can use this module with Version 3.5 or higher of FB 450 "RED_IN" in the
library "Redundant IO MGP" and Version 5.8 or higher of FB 450 "RED_IN" in
the library "Redundant IO CGP" V50.
Observe the following when measuring temperatures by means of
thermocouples and parameterized redundancy:
The value specified in "Redundancy" under "Tolerance window" is always based
on 2764.8 °C. For example, a tolerance of 27 °C is checked if "1" is entered, or a
tolerance of 138 °C is checked if "5" is entered.
A firmware update is not possible in redundant mode.
Online calibration is not possible in redundant mode.
Use in voltage measurement
The "wire break" diagnostics function in HW Config must not be activated
when operating the modules with thermocouples.
Use in indirect current measurement
Due to the maximum voltage range +/- 1 V, the indirect current measurement
can be carried out exclusively via a 50 ohm resistor. Mapping that conforms
to the system is only possible for the area +/- 20 mA.
AI 4x15Bit [EEx ib]
6ES7331-7RD00-0AB0
X
X
You cannot use the module for applications in hazardous areas in redundant
mode.
It is not suitable for indirect current measurement.
Use in direct current measurement
Suitable Zener diode: BZX85C6v2
Load capability of 4-wire transmitters: RB > 325 ohms
determined for worst case: 1 input + 1 Zener diode at an S7 overshoot value
24 mA to RB = (RE * I
max +
U
z max
)/I
max
Input voltage for 2-wire transmitters: Ue–2w < 8 V
determined for worst case: 1 input + 1 Zener diode at an S7 overshoot value
24 mA to Ue–2w = RE * I
max
+ U
z max
Note: You can only connect 2-wire transmitters with a 24 V external supply or 4-
wire transmitters. The internal power supply for transmitters cannot be used in
the circuit shown in figure 8-10, because this outputs only 13 V, and thus in the
worst case it would supply only 5 V to the transmitter.
AI 6x13Bit
6ES7 336–1HE00–0AB0
X
X
F module in standard mode
AI 8x0/4...20mA HART
6ES7 331–7TF01-0AB0
X
X
X
A firmware update is not possible in redundant mode.
Online calibration is not possible in redundant mode.
See
Distributed I/O Device ET 200M; HART Analog Modules
manual
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...