Using I/Os in S7–400H
13.4 Connecting redundant I/O to the PROFIBUS DP interface
S7-400H
System Manual, 03/2012, A5E00267695-11
191
Library V5.x Library V4.x Library V3.x Module
Order number
Distributed: Redundant AI dual-channel
AI8x12Bit
6ES7331–7KF02–0AB0
X
X
Use in voltage measurement
The "wire break" diagnostics function in HW Config must not be activated,
neither when operating the modules with transmitters nor when
thermocouples are connected.
Use for indirect current measurement
When determining the measuring error, observe the following: The total input
resistance in measuring ranges > 2.5 V is reduced from a nominal 100 kOhm
to 50 kOhm when operating two inputs connected in parallel.
The "wire break" diagnostics function in HW Config must not be activated,
neither when operating the modules with transmitters nor when
thermocouples are connected.
Use a 50 ohm resistor (measuring range +/- 1 V) or 250 ohm resistor
(measuring range 1 - 5 V) to map the current on a voltage, see figure 10-9.
The tolerance of the resistor must be added on to the module error.
This module is not suitable for direct current measurement.
Use of redundant encoders:
You can use a redundant encoder with the following voltage settings:
+/- 80 mV (only without wire break monitoring)
+/- 250 mV (only without wire break monitoring)
+/- 500 mV (wire break monitoring not configurable)
+/- 1 V (wire break monitoring not configurable)
+/- 2.5 V (wire break monitoring not configurable)
+/- 5 V (wire break monitoring not configurable)
+/- 10 V (wire break monitoring not configurable)
1...5 V (wire break monitoring not configurable)
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...