Technical data
20.1 Technical specification of the CPU 412–5H PN/DP; (6ES7 412-5HK06–0AB0)
S7-400H
386
System Manual, 03/2012, A5E00267695-11
PROFIBUS and Ethernet CPs, including CP
443–5 Extended
Maximum 14, of which max. 10 CPs as DP
masters
Connectable OPs
47
Time
Clock (real-time clock)
Yes
Buffered
Yes
Resolution
1 ms
Maximum deviation per day
Power off (backed up)
1.7 s
Power on (not backed up)
8.6 s
Operating hours counter
16
Number/number range
0 to 15
Range of values
SFC 2, 3 and 4:0 to 32767 hours
0 to 2
31
-1 hours when SFC 101 is used:
Granularity
1 hour
Retentive
Yes
Time synchronization
Yes
In AS, on MPI, DP and Ethernet MMS
As master or slave
On Ethernet over NTP
As client
Time difference in the system with
synchronization via MPI
Max. 200 ms
Time difference in the system with
synchronization via Ethernet
Max. 10 ms
S7 alarm functions
Number of stations that can be logged on
For block-related alarms with SFC (Alarm_S/SQ
and/or Alarm_D/DQ)
47
For block-related alarms with SFB (Notify,
Notify_8, Alarm, Alarm_8, Alarm 8P)
8
Block-related alarms with SFC
Yes
Simultaneously active Alarm_S/SQ blocks or
Alarm_D/DQ blocks
Maximum 250
Block-related alarms with SFB
Yes
Number of communication jobs for block-
related alarms with SFC and blocks for S7
communication (programmable)
Maximum 600
Default
300
Process control alarms
Yes
Number of archives that can be logged on
simultaneously (SFB 37 AR_SEND)
16
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...