Table A-1 MTBF factors of the redundant I/Os
Module
MLFB
MTBF factor
CCF = 1%
Digital input modules, distributed
DI 24xDC24V
6ES7 326–1BK00–0AB0
approx. 5
DI 8xNAMUR [EEx ib]
6ES7 326–1RF00–0AB0
approx. 5
DI16xDC24V, Alarm
6ES7 321–7BH00–0AB0
approx. 4
Analog input modules, distributed
AI 6x13Bit
6ES7 336–1HE00–0AB0
approx. 5
AI8x12Bit
6ES7 331–7KF02–0AB0
approx. 5
Digital output modules, distributed
DO 10xDC24V/2A
6ES7 326–2BF00–0AB0
approx. 5
DO8xDC24V/2A
6ES7 322–1BF01–0AA0
approx. 3
DO32xDC24V/0.5A
6ES7 322–1BL00–0AA0
approx. 3
Summary
There are now several thousand applications of redundant automation systems in the field,
in various configurations. To calculate the MTBF, we assumed an average configuration.
Based on experience in the field, an assumption of MTBF of 3000 hours is 95% reliable.
The system MTBF value calculated is about 230 years for a system configuration with
redundant CPU 417-5H.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...