Characteristic values of redundant automation systems
A.2 Comparison of MTBF for selected configurations
S7-400H
440
System Manual, 03/2012, A5E00267695-11
A.2
Comparison of MTBF for selected configurations
The following sections compare systems with a centralized and distributed I/Os.
The following framework conditions are set for the calculation.
●
MDT (Mean Down Time) 4 hours
●
Ambient temperature 40 degrees
●
Buffer voltage is safeguarded
A.2.1
System configurations with redundant CPU 417-5H
The following system with one CPU (e.g. 417-5H) operating in stand-alone mode forms the
basis for calculation of a reference factor, which defines the multiple of the system MTBF of
other systems with centralized I/Os compared to the base line.
Fault-tolerant CPU in stand-alone mode
Fault-tolerant CPU in stand-alone mode (e.g. CPU 417–5H)
Factor
85UDFN
3
6
$
&3
8
+
1
Redundant CPUs in different racks
Redundant CPU 417–5H in divided rack, CCF = 2%
Factor
[ILEHURSWLFFDEOHV
3
6
$
&3
8
+
3
6
$
&3
8
+
approx. 20
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...