Communication
14.1 Communication services
S7-400H
System Manual, 03/2012, A5E00267695-11
217
14.1.5
S7 routing
Properties
You can access your S7 stations beyond subnet boundaries using the programming device /
PC. You can use them for the following actions:
●
Downloading user programs
●
Downloading a hardware configurations
●
Performing tests and diagnostics functions
Note
On a CPU used as intelligent slave the S7 routing function is only available if the DP
interface is activated. In STEP 7, check the Test, Commissioning, Routing check box in
the properties dialog of the DP interface. For more information, refer to the
Programming
with STEP 7 manual, or directly to the STEP 7 Online Help
Requirements
●
The network configuration does not exceed project limits.
●
The modules have loaded the configuration data containing the latest "knowledge" of the
entire network configuration of the project.
Reason: All modules connected to the network gateway must receive routing information
which defines the paths to other subnets.
●
In your network configuration, the PG/PC you want to use to set up a connection via
gateway must be assigned to the network to which it is physically connected.
●
The CPU must set to master mode, or
●
if the CPU is configured as a slave, the "Programming, status/modify or other PG
functions" check box
must be activated in the properties of the DP interface for the DP slave in STEP 7.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...