System modifications during operation
17.8 Changing the CPU memory configuration
S7-400H
System Manual, 03/2012, A5E00267695-11
331
17.8.3
Changing the type of load memory
The following types of memory cards are available for load memory:
●
RAM card for the test and commissioning phase
●
FLASH Card for permanent storage of the completed user program
The size of the new memory card is irrelevant here.
If you change your memory configuration in this way, the system does not transfer any
program parts from the master CPU to the reserve CPU. Instead, it transfers only the
contents of the unchanged blocks of the user program (see section Switch to CPU with
modified configuration or expanded memory configuration (Page 152)).
It is your responsibility to download the entire user program to the new load memory.
Note
After reloading connections/gateways, it is no longer possible to change from a RAM card to
a FLASH card.
Starting situation
The fault-tolerant system is operating in redundant system mode.
The current status of the user program is available on the PG/ES as a STEP 7 project in
block format.
CAUTION
You cannot deploy a user program you uploaded from the target system here.
It is not permissible to recompile the user program from an STL source file, because this
action would set a new time stamp at all blocks and so prevent the block contents from
being copied when there is a master-reserve changeover.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...