Configuring with STEP 7
15.2 Programming device functions in STEP 7
S7-400H
264
System Manual, 03/2012, A5E00267695-11
15.2
Programming device functions in STEP 7
Display in SIMATIC Manager
In order to do justice to the special features of a fault-tolerant station, the way in which the
system is visualized and edited in SIMATIC Manager differs from that of a S7-400 standard
station as follows:
●
In the offline view, the S7 program appears only under CPU0 of the fault-tolerant station.
No S7 program is visible under CPU1.
●
In the online view, the S7 program appears under both CPUs and can be selected in both
locations.
Communication functions
For programming device (PG) functions that establish online connections (e.g. downloading
and deleting blocks), one of the two CPUs has to be selected even if the function affects the
entire system over the redundant link.
●
Data which is modified in one of the central processing units in redundant operation affect
the other CPUs over the redundant link.
●
Data which is modified when there is no redundant link (i.e. in single mode) initially
affects only the processed CPU. The blocks are applied by the master CPU to the
reserve CPU during the next link-up and update. Exception: No new blocks are applied
after changing the configuration. Loading the blocks is then the responsibility of the user.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...