Synchronization modules
18.2 Installation of fiber-optic cables
S7-400H
System Manual, 03/2012, A5E00267695-11
347
Storage of the fiber-optic cables
if you do not install the fiber-optic cable immediately after you received the package, it is
advisable to store it in a dry location where it is protected from mechanical and thermal
influences. Observe the permitted storage temperatures specified in the data sheet of the
fiber-optic cable. You should not remove the fiber-optic cables from the original packaging
until you are going to install them.
Open installation, wall breakthroughs, cable ducts:
Note the points outlined below when you install fiber-optic cables:
●
The fiber-optic cables may be installed in open locations, provided you can safely exclude
any damage in those areas (vertical risers, connecting shafts, telecommunications
switchboard rooms, etc.).
●
Fiber-optic cables should be mounted on mounting rails (cable trays, wire mesh ducts)
using cable ties. Take care not to crush the cable when you fasten it (see Pressure).
●
Always deburr or round the edges of the breakthrough before you install the fiber-optic
cable, in order to prevent damage to the sheathing when you pull in and fasten the cable.
●
The bending radii must not be smaller than the value specified in the manufacturer's data
sheet.
●
The branching radii of the cable ducts must correspond to the specified bending radius of
the fiber-optic cable.
Cable pull-in
Note the points below when pulling-in fiber-optic cables:
●
Always observe the information on pull forces in the data sheet of the corresponding
fiber-optic cable.
●
Do not reel off any greater lengths when you pull in the cables.
●
Install the fiber-optic cable directly from the cable drum wherever possible.
●
Do not spool the fiber-optic cable sideways off the drum flange (risk of twisting).
●
You should use a cable pulling sleeve to pull in the fiber-optic cable.
●
Always observe the specified bending radii.
●
Do not use any grease or oil-based lubricants.
You may use the lubricants listed below to support the pulling-in of fiber-optic cables.
–
Yellow compound (Wire-Pulling, lubricant from Klein Tools; 51000)
–
Soft soap
–
Dishwashing liquid
–
Talcum powder
–
Detergent
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...