Failure and replacement of components during operation
16.2 Failure and replacement of components during operation
S7-400H
System Manual, 03/2012, A5E00267695-11
269
16.2.3
Failure and replacement of an input/output or function module
Starting situation
Failure
How does the system react?
The S7-400H is in redundant system mode and
an input/output or function module fails.
Both CPUs report the event in the diagnostic
buffer and via appropriate OBs.
Procedure
CAUTION
Note the different procedures.
Minor injury or damage to equipment is possible.
The procedure for replacing and input/output or function module differs for modules of the
S7-300 and S7-400.
Use the correct procedure when replacing a module. The correct procedure is described
below for the S7-300 and the S7-400.
To replace signal and function modules of an S7-300, perform the following steps:
Step
What has to be done?
How does the system react?
1
Disconnect the module from its peripheral
power supply, if necessary.
2
Remove the failed module (in RUN mode).
Both CPUs process the swapping
interrupt OB 83 synchronized with each
other.
3
Disconnect the front connector and wiring. -
4
Plug the front connector into the new
module.
-
5
Insert the new module.
Both CPUs process the swapping
interrupt OB 83 synchronized with each
other.
Parameters are assigned automatically
to the module by the CPU concerned
and the module is addressed again.
To replace signal and function modules of an S7-400, perform the following steps:
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...