System modifications during operation
17.5 Adding components in STEP 7
S7-400H
310
System Manual, 03/2012, A5E00267695-11
17.5.9
STEP7, Using free channels on an existing module
The use of previously free channels of an I/O module depends mainly on the fact if the
module can be configured or not.
Non-configurable modules
Free channels can be switched and used in the user program at any time in case of non-
configurable modules.
Configurable modules
The hardware configuration first has to be matched to the used sensors or actuators for
configurable modules. This step usually requires a new configuration of the entire module in
most cases.
This means an uninterrupted operation of the respective modules is no longer possible:
●
One-sided output modules briefly output 0 during this time (instead of the configured
substitute or hold values).
●
Modules in switched DP stations are not reconfigured when you switch over to the CPU
with the modified configuration.
Proceed as follows to change the channel use:
●
In steps 1 to 5, you completely remove the respective module from the hardware
configuration and the user program. But it can remain inserted in the DP station.
●
In steps 3 to 8, you add the module with the modified use once again to the hardware
configuration and the user program.
NOTICE
The respective modules are not addressed between the two changeover steps (steps V
and 6); respective output modules output the value 0.
If this behavior is unacceptable for the process to be controlled, there is no other way to
use previously free channels. In this case you must install additional modules to expand
the system.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...