Failure and replacement of components during operation
16.2 Failure and replacement of components during operation
S7-400H
266
System Manual, 03/2012, A5E00267695-11
16.2.1
Failure and replacement of a CPU
Complete replacement of the CPU is not always necessary. If only the load memory fails, it
is enough to replace the corresponding memory card. Both cases are described below.
Starting situation for replacement of the CPU
Failure
How does the system react?
The S7-400H is in redundant system mode and a
CPU fails.
The partner CPU switches to single mode.
The partner CPU reports the event in the
diagnostic buffer and in OB 72.
Requirements for replacement
The module replacement described below is possible only if the "new" CPU
●
has the same operating system version as the failed CPU and
●
if it is equipped with the same load memory as the failed CPU.
NOTICE
New CPUs are always shipped with the latest operating system version. If this differs
from the version of the operating system of the remaining CPU, you will have to equip
the new CPU with the same version of the operating system. Either create an operating
system update card for the new CPU and use this to load the operating system on the
CPU or load the required operating system in HW Config with "PLC -> Update
Firmware", see section Updating the firmware without a memory card (Page 83).
Procedure
Follow the steps below to replace a CPU:
Step
What has to be done?
How does the system react?
1
Turn off the power supply module.
The entire subsystem is switched off
(system operates in single mode).
2
Replace the CPU. Make sure the rack
number is set correctly on the CPU.
–
3
Insert the synchronization modules.
–
4
Plug in the fiber-optic cable connections of
the synchronization modules.
–
5
Switch the power supply module on again.
CPU runs the self-tests and changes to
STOP.
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...